Page 15 - Crestron Home CoolAtomation
P. 15
Configure Setpoint & Room Temperature
On the BACnet Explorer Side
Identify Setpoint Configuration Values
Locate and click on CoolMasterNet from the Device list on the top right.
Locate and click on CoolMasterNet from the Address Space list on the bottom right
From CoolMasterNet’s sub-list, locate and click on XYZ set_temp/ room_temp,
where XYZ represents the indoor unit being configured 64 64
Object Identifier in the BACnet Property list
Notate the Type and Instance values
On the Crestron Home Side
Click on the Thermostat Setpoints menu
Set the Mode to Single
Input the Instance Number and Type discovered through your BACnet device 6 5
explorer for XYZ room_temp in the Temperature field
Input the Instance Number and Type discovered through your BACnet device
explorer for XYZ set_temp in the Heat Setpoint field